FAQs on PLC Hardware Specifications
 
 

Q10: Can the left-side extension modules for SV be connected to other slim type PLCs?
A: Currently only SV series PLC supports left-side extension. Left-side and right-side extensions differ completely in their hardware design. Therefore, the left-side extension can only be applied to SV.

Q11: Can the DVP01PU-H realize arc interpolation?
A: DVP01PU does not support interpolation but it does support constant speed, variable speed and interruption speed. If you need arc interpolation, please select DVP28SV or DVP-EH2.

Q12: Which register Device No. is for analog output of DVP-10SX? What is the resolution?
A:

Device No.
Function
D1056
Present value at analog input channel CH0
D1057
Present value at analog input channel CH1
D1110
Average value at analog input channel CH0
D1111
Average value at analog input channel CH1
D1116
CH0 of analog output
D1117
CH1 of analog output
D1118
Sampling time of analog/digital conversion (ms)
The resolution is 12 bits; I/O range: -20 ~ 20mA/-10 ~ 10V

Q13: What are the interruption subroutines in a Delta PLC?
A:
1. External input interruption: Designating any external input point, and the interruption subroutine will be triggered when the input is enabled.
2. Timed interruption: Designating time to trigger interruption.
3. Communication interruption: Using RS instruction to receive particular words for triggering interruption.
4. High-speed counter interruption: Using HSCS instruction to trigger interruption.
5. Pulse output interruption: Designating pulse output points to trigger interruption when the pulse output is enabled.

Q14: What are the differences between DVP-EH2 and DVP-EH? Can they share the same extension modules?
A: DVP-EH2 is very different from DVP-EH in terms of their hardware. DVP-EH2 spends shorter time in communicating with the extension module than does DVP-EH, and its efficiency is higher (approx. 1ms is needed for the communication). DVP-EH and DVP-EH2 cannot share extension modules because of the difference in hardware.

Q15: Bandwidth of I/O points for all PLC models:
A:

¡½
Delta PLC Input Point Specification

Model
Input point
Bandwidth
Input point
Bandwidth
SS/ES/EX
X0 ~ X1
20KHz
Others
10KHz
SA
X0 ~ X1
30KHz
Others
10KHz
SX
X0 ~ X1
30KHz
Others
10KHz
SC
X0 ~ X1
30KHz
Others
10KHz
X10 ~ X11
100KHz
--
--
SV
X0 ~ X1, X4 ~ X5
200KHz
Others
10KHz
X10 ~ X11, X14 ~ X15
20KHz
Others
10KHz
EH/EH2
X0 ~ X1, X4 ~ X5
200KHz
Others
10KHz
X14 ~ X15
20KHz
Others
10KHz

¡½ Delta PLC Output Point Specification

Model
Output point
Bandwidth
Output point
Bandwidth
SS/ES/EX
Y0
10KHz
Y1
10KHz
SA
Y0
30KHz
Y1
10KHz
SX
Y0
30KHz
Y1
10KHz
SC
Y0
30KHz
Y1
10KHz
Y10
100KHz
Y11
100KHz
SV

Y0 ~ Y1, Y2 ~ Y3, Y4, Y6

200KHz
Others
10KHz
EH/EH2 (excluding 20/32/40 point models)
All transistors
10KHz
--
--
EH/EH2 (20/32 point models)
Y0, Y2
200KHz
Others
10KHz
EH2 (40 point model)
Y0 ~ Y1, Y2 ~ Y3, Y4, Y6
200KHz
Others
10KHz

¡½ Delta PLC I/O Total Bandwidth

Model
Total bandwidth
SS/ES/EX
40KHz
SA
40KHz
SX
40KHz
SC
The first CPU
40KHz
The first CPU
130KHz
SV
20KHz (except HHSC, only X0 ~ X5)
EH/EH2
20KHz (except HHSC, only X0 ~ X5)

 
     
 
 
 
   
 